Enterasys Networks CSX7000 Manuale Utente Pagina 45

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 729
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 44
Central Site Remote Access Switch 45
H
ARDWARE
O
VERVIEW
System Platforms
CAUTION FOR DC-POWERED CSX5500S
Connect to a reliably-grounded SELV source.
Use branch circuit overcurrent protection rated at 15A only.
Use 12 or 14 AWG conductors only.
Incorporate a readily-accessible disconnect device in the field wiring that is suitably ap-
proved and rated.
Install in a restricted access area in accordance with the NEC or the authority having juris-
diction.
To reduce the risk of electrical shock or energy hazards:
!
CAUTION
Vedere la pagina 44
1 2 ... 40 41 42 43 44 45 46 47 48 49 50 ... 728 729

Commenti su questo manuale

Nessun commento